Experience the cosmic power With our Cable Power

Submersible Pump Cables

Rubber Flat / Round Submersible Pump Cables – 3 & 4 core

Applications

Jainflex Submersible Pump Cables are used for giving electrical connection to the submersible pump motors. up to the depth of 500 m and water temperature up to +75°C. These cables are ideal for outer installations in dry, moist and wet environments but however not suitable for explosive areas.

Features

• Bright-annealed 99.97% pure bare copper conductors these cables have low conductor resistance
• Quality backed by 22 years experience in cable industry
• Excellent resistant to moisture, abrasion, grease, oil.
• Longer Flexible Life
• Excellent mechanical & electrical properties
• Generally Conforming to: IEC 60227, BS 6500, UL-83, CENELEC HD 21, IS 694 and DIN VDE 0281.

Cable Structure

Conductor :

99.97% pure bare annealed EC grade copper.


Insulation :

Special Rubber EPR, EPDM core

Outer Sheath :

Special Rubber: Black, Blue Color
*Any other Color on specific request can also be supplied


Standard length cable packing :

Coils 100, 200,300 and 500, 1000m. In wooden drums

Technical Specification


Rubber Flat - 3 core & 4 core
Conductor Nominal Core Dia. Approx. Overall Dimensions of doubble Sheathed Cable Conductor Resistance at 20°C (max)
CCurrent rating at 40°C
Nominal Area in Nos. & Dia. of wire 3 Core 4 Core
(T x W) Thickness x Width (T x W) Thickness x Width
Sq. mm. Nos./mm mm mm mm Ω/km Amps.
1.5 22/0.30 3.25 6 x 12.8 6 x 15.8 12.1 14
2.5 36/0.30 3.84 6.4 x 14.6 6.5 x 18 7.41 18
4 56/0.30 4.5 7.4 x 16.8 7.6 x 21 4.95 26
6 84/0.30 5.3 7.9 x 18.7 7.9 x 24.3 3.3 31
10 140/0.30 6.5 9.9 x 23.7 9.9 x 29.7 1.91 42
16 224/0.30 8 11.4 x 28 11.8 x 36 1.21 57
25 350/0.30 10.1 14.7 x 35.5 14.7 x 45.1 0.78 72
35 490/0.30 11.3 16.2 x 39.5 16.2 x 50.1 0.554 90
50 703/0.30 13.6 18.3 x 45.5 18.3 x 58.1 0.386 115
70 988/0.30 15.3 20 x 51 20 x 66.5 0.272 143
95 1349/0.30 18 23.5 x 60 23.5 x 77.3 0.206 165

The number of wires is approximate and wire diameter is nominal. They shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
In view of continuous improvements in our design and process, specifications given here in are subject change without prior notice.


Rubber Round - 3 core & 4 core
Conductor Nominal Core Dia. Approx. Overall Dimensions of doubble Sheathed Cable Conductor Resistance at 20°C (max)
CCurrent rating at 40°C
Nominal Area in Nos. & Dia. of wire 3 Core 4 Core
Sq. mm. Nos./mm mm mm mm Ω/km Amps.
1.5 22/0.30 3.25 10 10.8 12.1 14
2.5 36/0.30 3.84 11 12.5 7.41 18
4 56/0.30 4.5 13 14.1 4.95 26
6 84/0.30 5.3 14.6 16 3.3 31
10 140/0.30 6.5 18 20.35 1.91 42
16 224/0.30 8 21.2 23.4 1.21 57
25 350/0.30 10.1 26 28.8 0.78 72
35 490/0.30 11.3 28.3 31.5 0.554 90
50 703/0.30 13.6 33.5 37.3 0.386 115
70 988/0.30 15.3 37.8 42.2 0.272 143
95 1349/0.30 18 43.5 48.8 0.206 165

The number of wires is approximate and wire diameter is nominal. They shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
In view of continuous improvements in our design and process, specifications given here in are subject change without prior notice.

Back to Top

list of tester

Enquiry

Now